eBay
Technical UL/CSA
·      General Use Rating UL/CSA:
(600 V AC) 25 A
·       Horsepower Rating UL/CSA:
(220 ... 240 V AC) Three Phase 2 hp
(440 ... 480 V AC) Three Phase 5 hp
(550 ... 600 V AC) Three Phase 7-1/2 hp
(120 V AC) Single Phase 3/4 hp
(200 ... 208 V AC) Three Phase 2 hp
(240 V AC) Single Phase 1-1/2 hp
·      Tightening Torque UL/CSA:
Auxiliary Circuit 11 IA
Control Circuit 11 IA
Main Circuit 13 IA
Environmental
·       Ambient Air Temperature:
Close to Contactor for Storage -60 ... +80 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
·       Climatic Withstand:
Category B according to IEC 60947-1 Annex Q
·       Maximum Operating Altitude Permissible:
3000 m
·       Resistance to Vibrations acc. to IEC 60068-2-6:
5 ... 300 Hz 4 g closed position / 2 g open position
·       Resistance to Shock acc. to IEC 60068-2-27:
Shock Direction: A 30 K40
Shock Direction: B2 15 K40
Shock Direction: C1 25 K40
Shock Direction: C2 25 K40
Closed, Shock Direction: B1 25 K40
Open, Shock Direction: B1 5 K40
·       RoHS Status:
Following EU Directive 2011/65/EU
Technical
·       Number of Main Contacts NO:
3
·       Number of Main Contacts NC:
0
·       Number of Auxiliary Contacts NO:
1
·       Number of Auxiliary Contacts NC:
0
·       Standards:
IEC 60947-1 / 60947-4-1 and EN 60947-1 / 60947-4-1, UL 508, CSA C22.2 N°14
·       Rated Operational Voltage:
Auxiliary Circuit 690 V
Main Circuit 690 V
·       Rated Frequency (f):
Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
·       Conventional Free-air Thermal Current (Ith):
acc. to IEC 60947-5-1, q = 40 °C 16 A
acc. to IEC 60947-4-1, Open Contactors q = 40 °C 35 A
·       Rated Operational Current AC-1 (Ie):
(690 V) 40 °C 25 A
(690 V) 60 °C 25 A
(690 V) 70 °C 22 A
·       Rated Operational Current AC-3 (Ie):
(220 / 230 / 240 V) 60 °C 9 A
(380 / 400 V) 60 °C 9 A
(415 V) 60 °C 9 A
(440 V) 60 °C 9 A
(500 V) 60 °C 9.5 A
(690 V) 60 °C 7 A
·       Rated Operational Power AC-3 (Pe):
(220 / 230 / 240 V) 2.2 KWT
(380 / 400 V) 4 KWT
(415 V) 4 KWT
(440 V) 4 KWT
(500 V) 5.5 KWT
(690 V) 5.5 KWT
(400 V) 4 KWT
·       Rated Operational Current AC-15 (Ie):
(220 / 240 V) 4 A
(24 / 127 V) 6 A
(500 V) 2 A
(690 V) 2 A
(400 / 440 V) 3 A
·       Rated Short-time Withstand Current (Icw):
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 150 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 35 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 60 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 300 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 80 A
for 0.1 s 140 A
for 1 s 100 A
·       Maximum Breaking Capacity:
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 250 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 106 A
·       Maximum Electrical Switching Frequency:
AC-1 600 cycles per hour
AC-2 / AC-4 300 cycles per hour
AC-3 1200 cycles per hour
AC-15 1200 cycles per hour
DC-13 900 cycles per hour
·       Rated Operational Current DC-13 (Ie):
(125 V) 0.55 A / 69 W
(24 V) 6 A / 144 W
(250 V) 0.27 A / 68 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(220 V) 0.27 A / 60 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
·       Rated Insulation Voltage (Ui):
acc. to UL/CSA 600 V
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
·       Rated Impulse Withstand Voltage (Uimp):
6 kV
·       Maximum Mechanical Switching Frequency:
3600 cycles per hour
·       Rated Control Circuit Voltage (Uc):
50 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
·       Operate Time:
Between Coil De-energization and NC Contact Closing 13 ... 98 ms
Between Coil De-energization and NO Contact Opening 11 ... 95 ms
Between Coil Energization and NC Contact Opening 38 ... 90 ms
Between Coil Energization and NO Contact Closing 40 ... 95 ms
·       Connecting Capacity Main Circuit:
Rigid 1/2x 1 ... 6 m²
Flexible with Ferrule 1/2x 0.75 ... 6 m²
Flexible with Insulated Ferrule 1x 0.75 ... 4 m²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 m²
·       Connecting Capacity Auxiliary Circuit:
Flexible with Ferrule 1/2x 0.75 ... 2.5 m²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 m²
Rigid 1/2x 1 ... 2.5 m²
·       Connecting Capacity Control Circuit:
Flexible with Ferrule 1/2x 0.75 ... 2.5 m²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 m²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 m²
Rigid 1/2x 1 ... 2.5 m²
·       Wire Stripping Length:
Auxiliary Circuit 10 mm
Control Circuit 10 mm
Main Circuit 10 mm
·       Degree of Protection:
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20
·      Terminal Type:
Screw Terminals
Dimensions
·       Product Net Width:
45 mm
·       Product Net Depth / Length:
77 mm
·       Product Net Height:
86 mm
·       Product Net Weight:
0.27 kg